DIGITAL OUTPUTS PERIPHERAL MODULE
DOM-PV module is designed to handle up to 8 digital outputs related to actuators of the PV system (remote resetting
of breakers, on / off remote control of devices, etc …), on command sent by the E2M-PV via ModBus on RS485 line.
The normal-status of each digital output can be configured independently of the others; commands sent by the E2M specify
the monostable or bistable mode: in the first case, the output will remain in the active state for 5 seconds, then it will return to its normal status; in the second case, the output will remain in active state until next command.
DOM-PV module is equipped with 2 LEDs:
- green LED is lit with high blink (2 Hz, 50% duty cycle) to indicate the absence of interrogation by the master, and with slow blink (200 ms every 4 seconds) in case of regular communication (reception of a correct message in the last 30 seconds);
- red LED is used to signal fails (eg, reception with errors) and is automatically reset at the absence of the error condition.
For further information, please download our technical data sheet (DOWNLOAD AREA, left sidebar)
- 8 open-collector digital ouputs 30 Vdc – 10 mA
- RS485 serial line (3 wires)
- 2 signaling LEDs:
- green for power / data link status
- red for alarm
- 12 Vdc power supply directly from the E2M-PV-module
- 2.5 kV insulation between power supply and digital ouput channels
- Connections:
- nr. 2 8-pin terminal blocks for digital ouputs
- nr. 1 10-pin terminal block for power / data cable incoming and outgoing:
(3-pin for RS485 + 2-pin for power) x 2, for input and output to the next node - Protocol: ModBus RTU, addressing by 4 dip-switches
- Enclosure: vertical DIN rail, IP30 degree of protection
For further information, please download our technical data sheet (DOWNLOAD AREA, left sidebar)
Please download our technical data sheet.
Download “tw_dom_pv_eng.pdf” tw_dom_pv_eng.pdf – Downloaded 916 times – 133.76 KB